HS-3030
![]() |
Description
The HS-3030 fire panel provides capability for up to 24 input circuits, 4 general purpose form “C” relays, 3 system operated relays (for Alarm, Trouble and Supervisory indication), 8 class B (style Y) or 4 class A (style Z) output bell circuits and 2 auxiliary power outputs. Input circuit modules are available for conventional or addressable inputs in class A (styles D or 6) or class B (styles B or 4). Field Programming: The HS-3030 panel’s database can be downloaded or optional uploaded in the field from a computer connected to service terminal using Network Plus software. All information is stored in non-volatile flash memory. The HS-3030 can be networked tomultiple HS-3030s, 3100s, and 3200 annunciators to provide additional input circuits, relays, bells and LEDs. One HS-3030 is designated the master panel for the network. All other HS-3030 panels will operate independently if communications with the master panel is lost. |
|
Features
|