MS-9050

Description

This compact, cost effective, intelligent addressable control panel supports up to 50 addressable devices of any type of detectors and modules. With an extensive list of powerful features, the MS-9050UD programs just like Fire•Lite’s larger products, yet fits into applications previously served only by conventional panels. The MS-9050UD’s integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The power supply and all electronics are contained on a single circuit board supported on a new quick install chassis and housed in a metal cabinet. Available accessories include remote annunciators and reverse polarity/city box transmitter. (4XTMF)

Features

  • Listed to UL Standard 864, 9th edition.

  • Auto-program (learn mode) reduces installation time. Reports two devices set to the same address.

  • On-board DACT.

  • 20 software zones.

  • Two independently programmable Style Z (Class A) or Style Y (Class B) NAC circuits.

  • Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices.

  • Remote Acknowledge, Silence, Reset and Drill via addressable monitor modules.

  • Two programmable relays and one fixed trouble relay.

  • Integral 80-character LCD display with backlighting.

  • Real-time clock/calendar with automatic daylight savings control.

  • History file with 500 event capacity.

  • Detector sensitivity test capability (NFPA 72 compliant).

  • Maintenance alert warns when smoke detector dust accumulation is excessive.

  • One person audible or silent walk test with walk-test log and printout.

  • Point trouble identification.

  • Waterflow (nonsilenceable) selection per monitor point.

  • System alarm verification selection per detector point.

  • PAS (Positive Alarm Sequence) and Pre-signal per point  (NFPA 72 compliant).

  • Up to eight ANN-BUS annunciators.

SLC COMMUNICATION LOOP:

  • Single addressable SLC loop which meets NFPA Style 4, 6, and 7 requirements.

  • 50 addressable device capacity (any combination of addressable detectors and modules).

  • Compatible with Fire•Lite’s addressable devices (refer to SLC Wiring Manual).

NOTIFICATION APPLIANCE CIRCUITS (NACS):

  • Two independently programmable output circuits. Circuits can be configured for the following outputs:

  • – Style Y (Class B)

  • – Style Z (Class A)

  • – Door Holder Service

  • – Aux Power Source

  • Silence Inhibit and Autosilence timer options.

  • Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability.

  • Selectable strobe synchronization per NAC.

  • 2.5 A total power for NACs.


PROGRAMMING AND SOFTWARE:

  • Autoprogram (learn mode) reduces installation time.

  • Custom English labels (per point) may be manually entered or selected from an internal library file.

  • Two programmable Form-C relay outputs.

  • 20 software zones.

  • Continuous fire protection during online programming at the front panel.

  • Program Check automatically catches common errors not linked to any zone or input point.