Description
Each Signaling Line Circuit (SLC) loop supports up to 159 addressable detectors including photoelectric, photoelectric with heat, ionization, photoelectric duct, fixed heat, fixed heat with rate-of-rise, and fixed high-heat detectors. It also supports up to 159 addressable modules including monitor (two-wire detector, normally open devices), dual-monitor functions (two monitor circuits from one module, two addresses used), control (for Notification Appliance Circuits), and relay (two Form-C) modules. The panel uses surface-mount technology and is designed for ease of installation, programming, and maintenance. It features the latest in advanced fire protection technology, including maintenance alert and automatic detector test functions.
|
|
Features
SLC Loop:
-
SLC can be configured for NFPA Style 4, 6, or 7 operation.
-
SLC supports up to 318 addressable devices per loop (159 detectors and 159 monitor, control, or relay modules), including the new addressable dual-monitor module, heat detectors, and duct detector.
-
SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG (3.31 mm²). Requires twisted, shielded wire (3,000 ft./914.4 m untwisted, unshielded wire).
Notification Appliance Circuits (NACs):
-
Four onboard NACs with additional NAC capability using output control modules (CMF-300 or CMF-300-6).
-
Silence Inhibit and Auto Silence timer options.
-
Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability.
-
Selectable strobe synchronization per NAC.
Advanced Fire Technology:
-
Sensitivity testing with printable results, onsite or offsite.
-
Automatic drift compensation.
-
Autoprogram (learn mode) reduces installation time.
-
Fully programmable from local keypad, local PS-2 keyboard or PC via PK-Plus Windows® utility.
-
Remote site upload/download capability (with DACT-UD).
-
Two-level user-programmable passwords.
-
Custom English labels (per point) may be manually entered or selected from an internal library file.
-
Two programmable Form-C relay outputs.
-
99 software zones.
User Interface:
-
Optional modem (DACT-UD).
-
Remote Acknowledge, Silence, Reset and Drill via addressable monitor modules, ACS Series annunciators or LCD-80F remote annunciator.
-
EIA-232 printer/PC interface (variable baud rate) on main circuit board.
-
Integral 80-character LCD display with backlighting.
-
Real-time clock/calendar with automatic daylight savings adjustments.
-
History file with 1,000-event capacity.
-
EIA-485 supporting up to 32 ACS Series annunciators.
-
EIA-485 supporting up to 32 LCD-80F annunciators.
-
Maintenance alert warns when smoke detector dust accumulation is excessive.
-
Automatic device type-code verification.
-
One person audible or silent walk test with
walk-test log and printout.
-
Point trouble identification.
-
Local piezo sounder.
-
Waterflow (nonsilenceable) selection per monitor point.
-
System alarm verification selection per detector point.
-
PAS (Positive Alarm Sequence) and presignal delay per point (NFPA 72 compliant).
|
|